𝗖𝗢𝗡𝗧𝗔𝗠 𝘃𝘀 𝗙𝗗𝗦: 𝗶𝘀 𝗮𝗻 𝗮𝗶𝗿𝗳𝗹𝗼𝘄 𝗻𝗲𝘁𝘄𝗼𝗿𝗸 𝗲𝗻𝗼𝘂𝗴𝗵 𝗳𝗼𝗿 𝘀𝘁𝗮𝗶𝗿 𝗽𝗿𝗲𝘀𝘀𝘂𝗿𝗶𝘇𝗮𝘁𝗶𝗼𝗻? 🏢🔥
We modelled the 𝘕𝘙𝘊 𝘊𝘢𝘯𝘢𝘥𝘢 10-𝘴𝘵𝘰𝘳𝘦𝘺 𝘧𝘪𝘳𝘦 𝘵𝘰𝘸𝘦𝘳 with both 𝗖𝗢𝗡𝗧𝗔𝗠 and 𝗙𝗗𝗦, using the same published leakage areas, and checked them against the original 𝘛𝘢𝘮𝘶𝘳𝘢 & 𝘒𝘭𝘰𝘵𝘦 measurements.
▪️ 𝗗𝗼𝗼𝗿𝘀 𝗰𝗹𝗼𝘀𝗲𝗱, 𝘂𝗻𝗶𝗳𝗼𝗿𝗺 𝘁𝗲𝗺𝗽𝗲𝗿𝗮𝘁𝘂𝗿𝗲𝘀: CONTAM is spot on, within 𝟬.𝟱 𝗣𝗮 of FDS for pure stack effect, and it runs in seconds
▪️ 𝗢𝗽𝗲𝗻 𝘀𝘁𝗮𝗶𝗿 𝗱𝗼𝗼𝗿: FDS computes a discharge coefficient of 𝟬.𝟴𝟱–𝟬.𝟵𝟬, the measured value is 𝟬.𝟴𝟱. CONTAM with the usual 𝟬.𝟲𝟱 overestimates the door Δp by 𝟲𝟬–𝟳𝟬%
▪️ 𝗖𝗼𝗹𝗱 𝘀𝘂𝗽𝗽𝗹𝘆 𝗮𝗶𝗿 𝗮𝘁 −𝟭𝟬 °𝗖: in FDS it pools at the bottom of the stair and reverses the stack effect on the first floors. A single-zone stair in CONTAM can't see it: 𝟰–𝟴 𝗣𝗮 error
▪️ 𝗙𝗶𝗿𝗲 𝗼𝗻 𝗳𝗹𝗼𝗼𝗿 𝟮: measured critical supply 𝟯.𝟰𝟴 𝗺³/𝘀. FDS stops the smoke at ~𝟯.𝟱–𝟰 𝗺³/𝘀, CONTAM asks for 𝟰.𝟰–𝟱.𝟭 𝗺³/𝘀 (25–45% conservative)
The message: use CONTAM to size the fan with doors closed, and FDS to check open doors, cold supply air and fire.
The whole FDS study ran on 𝗰𝗹𝗼𝘂𝗱𝗛𝗣𝗖 for €𝟭𝟬.𝟰𝟬.